UL 3484

HUAHAO-- CABLE E231903    AWM
UL 3484
1.Rated temperature:125ºC
2.Rated voltage:600V
3.According to:UL subject 758,UL1581,UL62
4.Solid or Stranded,tinned or bare copper conductor 30-4/0AWG
5.EP Insulated Wire.
6.Passes UL VW-1 & CSA FT1 Vertical flame test
7.Uniform insulation thickness of wire to ensure easy stripping and cutting.
8.Environmental testing pass ROHS
9.Use for general electric equipment internal wiring.
Item Gauge Conductor Area Conductor Frame conductor
outer
diameter
insulation
thickness
wire O.D Max Cond.
resistance
No. (AWG) (mm2) wire core qty wire diameter (mm) (mm) (mm) (Ω/km)
1 26 0.145 7 0.160 0.48 0.76 2.00 139.00
2 24 0.228 11 0.160 0.61 0.76 2.15 88.90
3 22 0.352 17 0.160 0.76 0.76 2.30 57.50
4 20 0.538 21 0.178 0.94 0.76 2.50 34.60
5 18 0.835 16 0.254 1.16 0.76 2.75 23.30
6 16 1.357 26 0.254 1.49 0.76 3.05 17.40
7 14 2.140 41 0.254 1.87 0.76 3.50 15.10
8 12 3.392 65 0.254 2.36 0.76 4.00 9.20
9 10 5.644 105 0.254 3.00 0.76 5.00 5.40
10 8 8.924 119 0.300 4.25 1.15 6.80 4.10
11 6 14.299 266 0.254 5.41 1.15 8.00 2.42
12 4 22.578 420 0.254 6.80 1.15 10.40 0.937
13 2 35.462 266 0.400 8.56 1.15 12.00 0.595
14 1 44.394 333 0.400 9.60 1.40 12.80 0.472
15 1/0 55.726 418 0.400 10.77 1.40 14.00 0.374
16 2/0 71.191 534 0.400 12.19 1.40 15.50 0.30
17 3/0 89.322 670 0.400 13.67 1.98 18.00 0.238
18 4/0 111.653 536 0.500 15.26 1.40 18.50 0.189