UL 3286

HUAHAO-- CABLE        E231903 --- LL217627
UL 3286
1.Rated temperature:105ºC
2.Rated voltage:300v
3.According to:UL subject 758,UL1581,CSA22.2
4.Solid or Stranded,tinned or bare copper conductor 32-10AWG
5.Irradiated Polyethylene Insulated Wire
6.Passes UL VW-1 & CSA FT1 Vertical flame test
7.Uniform insulation thickness of wire to ensure easy stripping and cutting.
8.Environmental testing pass ROHS
9.Use for general electric equipment internal wiring.
Item Gauge Conductor Area Conductor Frame conductor
outer
diameter
insulation
thickness
wire O.D Max Cond.
resistance
No. (AWG) (mm2) wire core qty wire diameter (mm) (mm) (mm) (Ω/km)
1 30 0.057 7 0.10 0.30 0.41 1.3 354
2 28 0.091 7 0.13 0.38 0.41 1.4 223
3 26 0.145 7 0.160 0.48 0.41 1.5 139.00
4 24 0.228 11 0.160 0.61 0.41 1.6 88.90
5 22 0.352 17 0.160 0.76 0.41 1.8 57.50
6 20 0.538 21 0.178 0.94 0.41 2.0 34.60
7 18 0.835 16 0.254 1.16 0.41 2.2 23.30
8 16 1.357 26 0.254 1.49 0.41 2.5 17.40
9 14 2.140 41 0.254 1.87 0.41 2.9 15.10
10 12 3.392 65 0.254 2.36 0.41 3.4 9.20
11 10 5.644 105 0.254 3.00 0.41 4.0 5.40